E2F Series Cooling Towers

E2F Series Cooling Towers
100 to 240 tons

An ideal and cost-efficient alternative to metal cooling towers, the fiberglass Conair E2F Series Cooling Tower is available for applications ranging from 100 to 240 tons. The E2F Series is designed for outdoor use in industrial manufacturing locations.

All water connections, the water distribution system, and the cellular fill are made to resist rot, decay, and biological attack.

No on-site construction or fabrication is necessary because the entire tower is delivered in one piece. The fan and motor are shipped separately to prevent possible shipping damage.

  • Designed to perform and keep performing
  • Further improve the performance
  • 10-year shell warranty
  1. Downloads
  2. Videos
  3. Contact Us

Specifications sheet

 

Current manual

English

Contact Us Form

Click here

email

info@conairgroup.com

Phone

+1 724 584 5500

Parts & Service

+1 800 458 1960 - United States

+1 814 437 6861 - International

parts@conairgroup.com

service@conairgroup.com

Features (click here to hide)

Optional inlet and outlet flanges.

Access door to the tower with stainless steel fasteners.

Durable fiberglass shell resists corrosion and harsh weather conditions.

PVC fill media maximizing air/water contact which optimizes heat transfer.

Leak-proof one piece basin that can be mounted on two I-beams or an optional structural steel base.

Completely inclosed fan motor with bearings that are permanently lubricated and require no maintenance.

Louvers made of durable PVC are designed to eliminate possible back splash and are removable to allow full access to the basin.

PVC water distribution system includes large non-clogging nozzles that efficiently and uniformly distribute water across all fill surfaces.

Options (click here to hide)

Stainless steel outlet strainer.

Pre-assembled, painted structural steel base.

NEMA 3R thermostat.

Water make-up float valve aseembly.

Basin heater package.

Equalization connection.

Inlet and outlet flanges.

High temperature option (up to 150°F {66°C}).

Specifications (click here to hide)
E2F-100, E2F-115, E2F-125, E2F-140
Front view Side view Top view
     
E2F-170, E2F-185, E2F-205, E2F-240
Front view Side view Top view

 

Models E2F-100 E2F-115 E2F-125 E2F-140
Performance characteristics     
Tower capacity  tons 100  115  125  140 
Sump capacity  gallons {liters}   333 {1260} 333 {1260}  333 {1260}  333 {1260} 
Blower motor  Hp {kW}  3 {2.24}  5 {3.73}  5 {3.73}  7.5 {5.59} 
Wet bulb temperature / Output tower tons {gpm}     
70°F {21°C}   155 {467} 179 {540}  185 {560}  200 {600} 
72°F {21°C}   143 {430} 165 {497}  172 {520}  187 {565} 
75°F {21°C}  123 {370}  141 {427}  150 {454}  165 {500} 
78°F {21°C}  100 {300}  115 {345}  125 {375}  140 {420} 
80°F {21°C}   83 {251} 95 {288}  106 {320}  120 {363} 
Dimensions  inches {mm}     
A - Height  122.75 {3118}  125 {3175}  125 {3175}  128.25 {3258} 
B - Width  114.5 {2908}  114.5 {2908}  114.5 {2908}  114.5 {2908} 
C - Depth  90 {2286}  90 {2286}  90 {2286}  90 {2286} 
Weight  lbs {kg}     
Shipping (dry)  1760 {799}  1910 {867}  1910 {867}  2150 {975} 
Operating  4535 {2057}  4535 {2057}  4685 {2125}  4925 {2234} 
Power requirements  Full Load Amps     
230V/3 phase/60 Hz   12.0 18.0  18.0  24.0 
460V/3 phase/60 Hz   6.0 9.0  9.0  12.0 
Connections  inches {mm}     
Water inlet  4 PVC {120}
Water outlet  8 PVC {203}
Drain connection  2 FPT {51}
Water requirements     
Minimum inlet pressure  psi {bar}  6.0 {0.41}  4.0 {0.28}  4.0 {0.28}  5.0 {0.34} 
Maximum flow rate  gpm {l/min}  600 {2270}
Maximum inlet temperature  110°F {43°C}

 

 

Models E2F-170 E2F-185 E2F-205 E2F-240
Performance characteristics     
Tower capacity  tons 170  185  205  240 
Sump capacity  gallons {liters}   340 {1285} 340 {1285}  340 {1285}  340 {1285} 
Blower motor  Hp {kW}  7.5 {5.59}  10 {7.45} 10 {7.45} 15 {11.18}
Wet bulb temperature / Output tower tons {gpm}     
70°F {21°C}  256 {725} 274 {725} 290 {725} 325 {725}
72°F {21°C}  241 {725} 257 {725} 272 {725} 305 {725}
75°F {21°C}  208 {630} 228 {688} 245 {725} 273 {725}
78°F {21°C}  170 {510} 185 {555} 205 {615} 240 {720}
80°F {21°C}  141 {426} 153 {463} 174 {525} 204 {616}
Dimensions  inches {mm}     
A - Height  124.5 {3162} 127.5 {3239} 127.5 {3239} 127.5 {3239}
B - Width  139.5 {3543} 139.5 {3543} 139.5 {3543} 139.5 {3543}
C - Depth  100.5 {2553} 100.5 {2553}  100.5 {2553}  100.5 {2553} 
Weight  lbs {kg}     
Shipping (dry)  2660 {1207} 2700 {1225} 2700 {1225} 2750 {1248}
Operating  5230 {2373} 5530 {2509}  5570 {2527} 5570 {2527}
Power requirements  Full Load Amps     
230V/3 phase/60 Hz   24.0 34.0 34.0 48.0
460V/3 phase/60 Hz  12.0 17.0 17.0  24.0 
Connections  inches {mm}     
Water inlet   Two - 4 PVC {120}
Water outlet  8 PVC {203}
Drain connection  2 FPT {51}
Water requirements     
Minimum inlet pressure  psi {bar}  5.0 {0.34}  6.0 {0.41}  7.0 {0.48} 10.0 {0.69}
Maximum flow rate  gpm {l/min}  725 {2740}
Maximum inlet temperature  110°F {43°C}