This uniquely designed media filter is ideal for removing suspended solids in the cooling system.
The special media removes solids down to 0.5 microns. As particulates are removed from the process water, the unit
will automatically backflush to self-clean based on time or increasing pressure drop.
Contact Us Form
Phone
+1 724 584 5500
Parts & Service
+1 800 458 1960 - United States
+1 814 437 6861 - International
| MODELS | SMF-20 | SMF-24 | SMF-30 | SMF-36 | SMF-42 | SMF-48 |
| Performance characteristics | ||||||
| Cooling tower (ton) maximum | ||||||
| Harsh environment (lots of dirt in the air) | to 230 | to 360 | to 520 | to 750 | to 1000 | to 1280 |
| Clean environment (mild amount of dirt) | to 280 | to 460 | to 650 | to 940 | to 1280 | to 1590 |
| Pump Hp {kW} | 1 {.75} | 2 {1.5} | 3 {2.3} | 3 {2.3} | 5 {3.8} | 5 {3.8} |
| Flow rate GPM {l/min} | 43 {162.8} | 63 {238.5} | 98 {370.9} | 142 {537.5} | 192 {726.8} | 251 {950.1} |
| Filter area ft² {m²} | 2.2 {0.2} | 3.14 {0.29} | 4.91 {0.46} | 7.10 {0.66} | 9.60 {0.89} | 12.05 {1.12} |
| Media volume ft³ | 2 {0.06} | 2.5 {0.07} | 4 {0.11} | 4.5 {0.41} | 13.5 {0.38} | 17 {.48} |
| Pipe connection sizes NPT inches | ||||||
| Inlet | 2 | 2 | 2 | 3 | 3 | 3 |
| Outlet | 2 | 2 | 2 | 3 | 3 | 3 |
| City | 2 FLG | 2 FLG | 2 FLG | 3 FLG | 3 FLG | 3 FLG |
| Waste | 2 | 2 | 2 | 3 | 3 | 3 |
| Dimensions inches {mm} | ||||||
| A - Height | 54 {1371} | 54 {1371} | 54 {1371} | 65 {1651} | 65 {1651} | 65 {1651} |
| B - Width | 66 {1676} | 69 {1752} | 72 {1828} | 77 {1955} | 77 {1955} | 83 {2108} |
| Depth | 30 {762} | 30 {762} | 35 {889} | 48 {1219} | 48 {1219} | 48 {1219} |
| Water requirements | ||||||
| Backflush volume in two minutes gal.{l} | 86 {325.5} | 126 {477.0} | 196 {742.0} | 284 {1075.1} | 384 {1453.6} | 502 {1900.2} |
| City water required @40 psi gpm {l/min} | 43 {162.8} | 63 {238.5} | 98 {370.9} | 142 {537.5} | 192 {726.8} | 251 {950.1} |
| Weight lb {kg} | ||||||
| Installed | 445 {202} | 597 {271} | 992 {450} | 2041 {926} | 2970 {1347} | 4995 {2266} |
| Shipping | 350 {159} | 470 {213} | 740 {336} | 1550 {703} | 2265 {1027} | 3875 {1758} |
| Voltages Total amps based on motor size | ||||||
| 230V/3 phase/60 Hz | 4.2 | 6.8 | 6.8 | 9.6 | 15.2 | 15.2 |
| 480V/3 phase/60 Hz | 2.1 | 3.4 | 3.9 | 3.9 | 6.9 | 6.9 |
| 575V/3 phase/60 Hz | 1.7 | 2.7 | 3.9 | 3.9 | 6.1 | 6.1 |